What Does “PASS” Mean on a Cable Test?

Read a sample report, understand its limits and ask for the evidence your project actually needs.

Reviewed September 2026 · 3 minute read

Read this sample before accepting the result

Direct link
FryAVSI practice record C-014 · invented values for this exercise
FieldSample entryWhat to ask
Cable IDC-014 · office jack J14 ↔ rack panel P1/14Do the labels at both ends match?
MethodBasic wiremapDoes this method meet the project requirement?
ResultPASS: reported pin-to-pin wiringWhich wiring faults can this particular instrument detect?
Performance limitNot measuredWas an application qualification or category certification required?
Instrument / dateTraining tester / example dateDoes the real record identify the instrument and test date?

Conclusion: this record supports its stated wiring result. It does not prove Cat6 performance, a particular application speed or the quality of every other cable in the building.

Ask what was tested

Direct link

Verification

Basic physical or wiring checks within the instrument’s capability. Some simple continuity testers cannot identify a split pair.

Qualification

Whether a link supports a specified application under the qualification method used.

Certification

Measurements against a selected cabling category or class limit using the required configuration and capable instrument.

The testing-level lesson explains how to specify the method and handoff before work starts.

Nine good reports do not cover ten cables

Direct link

Worked example

A ten-outlet office handoff

Your agreed cable list is C-001 through C-010. The contractor supplies nine passing reports and an unlabeled screenshot. Match the reports to the register. Ask for the missing identified result; do not infer that the screenshot belongs to C-010.

Your five-point report check

Direct link
  1. Identity: exact cable and both endpoints.
  2. Requirement: application, category/class or agreed test objective.
  3. Setup: instrument, adapters, selected limit and link/channel configuration as applicable.
  4. Coverage: all specified measurements and all links, with repaired links retested.
  5. Handoff: readable results plus original result files where required, exceptions and acceptance status.
A report says Cat6 PASS but does not identify link or channel. What next?

Ask for the original report and configuration. The test setup and selected requirement affect what the result means.

Put it into practice

Check what you learned

Choose an answer for each question, then check your understanding. Your answers stay in this browser.

1. The sample C-014 wiremap passes. Which statement is supported?
2. Ten cable IDs are specified; only nine identified results arrive. What should happen?
3. When should test requirements be agreed?

Read the answers and explanations
  1. The test reports the wiring result within that instrument’s capability.

    A result must be read within the scope of the measurement performed.

  2. Resolve the missing test evidence before accepting complete coverage.

    A complete handoff accounts for every required link.

  3. Before quotation and installation, so method and evidence are in scope.

    The required evidence affects instruments, labor, documentation and acceptance.

Sources and further reading

Keep your momentum

Ready for the next step?

If you can explain the example and your answer, try the next lesson. Revisit the feedback whenever you need it.

FryAVSI · Updated September 10, 2026

Reference this lesson or use a section’s direct link for a particular chart or example. How to cite an example.